Chapter 3 Site Preparation
Power and Grounding
As Figure 3-3 shows, the non isolated system has a 48 VDC return that internally connects to the
backplane. (This design calls for a hard-wired return and so does not allow for an optional or alternate
ground connection.) The internal connection provides a low-impedance connection between 48 VDC
return and frame ground. This grounding scheme protects the signals on the backplane from corruption
by transients that can result from lightning or electrostatic discharge.
To improve protection against transients, the loop area (and resultant loop impedance) should be made
as small as possible by locating the –48 VDC supply, 48 VDC return, and protective earth conductors as
close to each other as possible.
As recommended in ITU-T K.27, the multi point grounding in a mesh bonding network provides the best
protection for equipment by providing the lowest impedance in the ground system. For more detailed
information, refer to the recommendation itself.
Conductor Characteristics for Carrying Current and Ensuring Low Voltage Drops
To prevent signal degradation, a conductor must be large enough to prevent its impedance from creating
a voltage drop equal to 2 percent of the reference voltage. Also, the protective earth conductor must be
large enough to carry all the current if the 48 VDC return fails. This latter requirement is for safety. Full
fault redundancy is achieved by having equal size conductors for the protective earth ground and the 48
VDC return of the switch.
For wire gauges that prevent unacceptable voltage drops over different lengths of copper wire, see
Table 3-2. For the resistance of 1000 feet of copper wire for each gauge of wire, see Table 3-3. These
references are for planning purposes and may be further subject to local laws and practices.
Table 3-2 Wire Gauge for Current Loads Over Copper Wire Lengths
DC Current Distance in Feet
25 feet 50 feet 75 feet 100 feet 150 feet 200 feet 400 feet
5A 18 14 14 12 10 8 6
10A1412108862
15A141088642
20A12886420
25A12864420
30A108642200
35A1064221000
40A862220000
45A8642100000
50A8442100______
55A8422000______
60A8422000______
65A64210000______
70A642100000______
75A642100000______
100A42100000____________