Cisco MGX 8230 Specifications Page 145

  • Download
  • Add to my manuals
  • Print
  • Page
    / 282
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 144
4-13
Cisco MGX 8230 Edge Concentrator Installation and Configuration
Release 1.1.31, Part Number 78-11215-03 Rev. B0, May 2001
Chapter 4 Enclosure Installation
Rack Mounting an MGX 8230
Figure 4-9 Polarities at MGX 8230 PEM Pluggable Terminal Block
Step 4
Locate the wiring block for TB1. Figure 4-10 illustrates the TB1 wiring block (that is, the mating plug
that attaches to TB1).
Figure 4-10 Pluggable Terminal Block on MGX 8230 PEM
Step 5
Insert and secure the stripped ends of the 10 AWG wire in the wiring block as shown in Figure 4-9 and
Figure 4-10. Figure 4-10 shows the assembly with an example wire and the screw that secures it in the
pluggable wire block.
Step 6 Plug the pluggable terminal block to the receptacle TB1 on the PEM.
Step 7 If you have a redundant DC PEM installed in your MGX 8230, repeat step 1 through step 6 for the second
DC PEM.
Step 8 For each DC PEM, connect the DC input wiring to a separate dedicated DC source capable of supplying
at least 30 Amps (typical). The 48VDC power source in the building should have a 30 Amp DC circuit
breaker. The buildings wiring should include an easily accessible disconnect device. Make sure the
safety ground wire connects to a reliable building (earth) ground.
Warning
For personnel safety, the green or green/yellow wire must connect to safety (earth) ground at both
the equipment and at the supply side of the DC wiring.
26265
123
-48 VDC
-48 VDC
return
Safety
ground
10 AWG
or 4 sq. mm.
48 VDC Return
Safety ground
48 VDC
3
2
1
26264
Page view 144
1 ... 144 145 146 ... 282

Comments to this Manuals

No comments