Cisco AS5800 Operations, Administration, Maintenance, and Provisioning Guide
DOC-7810814=
Chapter 5 Maintenance
Replacement Procedures
Step 4 If you are using the optional AC-input power shelf, connect the monitor cable DB-9 connector at the
base of the filter module and tighten the jackscrews. Verify that the DB-25 connector at the other end of
the cable is connected to the AC-input power shelf (see Figure 5-9). Power ON the AC-input power shelf.
Step 5 Power ON ( | ) the power switches located on each dial-shelf PEM front panel.
Step 6 Note the service maintenance on your Site Log sheet.
This completes the procedure for removing and replacing the filter module.
Replacing an AC-Input Power Supply
The AC-input power shelf is an optional component of the Cisco AS5800 and is used to convert
AC-input power into DC-output power for the DC-powered Cisco 5814 dial shelf. The AC-input power
shelf contains two AC-input power supplies.
This section explains how to remove and replace an individual power supply in the power shelf.
Tools and Parts Required
To remove and replace an individual power supply you need the following tools and parts:
AC power supply (DS58-AC-PWR=)
ESD-preventive wrist strap
If access to the power supply bays is partially blocked by a power strip or other permanent rack
fixture, you need a 1/4-in., flat-blade screwdriver to temporarily detach the fixture from the
equipment rack-mounting strips.
Removing and Replacing a Power Supply
Use the following procedure if you are replacing a faulty power supply, or if you want to reduce the
weight of the power shelf before you install it in a rack. If you do not want to remove power supplies
prior to rack-mounting the AC-input power shelf, skip this section and continue with the Replacing a
Dial-Shelf Controller Card section on page 5-15.
The AC-input power shelf is configured with two power supplies. You can remove or replace one of the
power supplies without affecting system operation. When power is removed from one supply, the
redundant power feature causes the second power supply to ramp up to full power and maintain
uninterrupted system operation.
To remove a power supply, perform the following steps:
Caution A single power supply weighs 14.5 lb (6.6 kg). Use both hands when removing or replacing
a power supply.
Step 1 Attach an ESD-preventive wrist strap between you and an unpainted chassis surface.
Step 2 Ensure that the power switch for the power supply you are removing is in the OFF (O) position.